The RC48C ground-fault ground-c ontinuity monitor is used to monitor the residual current in high-resistance grounded instal- lations. The maximum ground faul t current in these installations is limited by a neutral grounding resistor to 5 A, 15 A or 25 A.

It is particularly suitable for trailing cable protection. Trailing cables are very susceptible to environmental damage and therefore they need special attention. This is where BENDER comes in.

The RC48C ground-fault ground -continuity monitor combines two functions in one device:

  1. Monitoring of the residual current and
  2. Monitoring the grounding conductor for low resistance, high resistance and shorted.

If a limiting value is exceeded, a relay with two voltage free chan- geover contacts will be activated. Alarm messages of the RC48C ground-fault ground-c ontinuity monitor can also be displayed on a remote RI2000GC alarm indicator and operator panel.

Questions? Contact us!

RC48C
RC48C

The RC48C ground-fault ground-c ontinuity monitor is used to monitor the residual current in high-resistance grounded instal- lations. The maximum ground faul t current in these installations is limited by a neutral grounding resistor to 5 A, 15 A or 25 A.

It is particularly suitable for trailing cable protection. Trailing cables are very susceptible to environmental damage and therefore they need special attention. This is where BENDER comes in.

The RC48C ground-fault ground -continuity monitor combines two functions in one device:

  1. Monitoring of the residual current and
  2. Monitoring the grounding conductor for low resistance, high resistance and shorted.

If a limiting value is exceeded, a relay with two voltage free chan- geover contacts will be activated. Alarm messages of the RC48C ground-fault ground-c ontinuity monitor can also be displayed on a remote RI2000GC alarm indicator and operator panel.

Questions? Contact us!

Features

  • Earth fault monitor with integrated loop monitoring
  • Measurement of the fault current by means of a Bender measuring current transformer
  • Alarm easily recognisable by LED lights
  • Alarm relay with two voltage-free changeover contacts
  • Alarm contact can be delayed by a selectable time
  • Detection of series and transverse resistance faults
  • The alarm relay can be used to trigger a load switch
  • Depending on the type of load switch, the operating mode of the alarm relay can be set to normally open or normally closed operation

Applications

  • Monitoring cables that feature a pilot wire
  • Monitoring of earthing systems

RC48C Variant(s)

Basic deviceSupply voltage/
frequency range US
Power consumptionArt. No.
Residual current/loop monitoring deviceAC/DC 60…264 V
50…60 Hz
approx. 5 VA at AC 60 V
approx. 8.5 VA at AC 264 V
B94013002

Optional Accessories for RC48C

Type designationArt.-No.
Termination device, P = 5 WB94013008
Termination device, P = 50 WB94013009
Termination device, P = 50 WB94013006
Termination device with integrated resistor, P = 50 WB94013007
Remote alarm indicator and operator panelB94071000
Residual current transformer, 70 mmB911777
Residual current transformer, 105 mmB911778

Downloads for RC48C

NameCategorySizeLanguageTimestampD-/B-Number
RC48 CE Declarations of conformity 84.0 KB 2022/08/1212.08.2022
RC48C Manuals 606.6 KB EN2024/03/0101.03.2024D00318
RC48C Manuals 606.6 KB DE2024/03/0101.03.2024D00318
RC48C Manuals 722.4 KB EN2020/02/2626.02.2020
RC48C Manuals 722.4 KB ES2020/02/2626.02.2020