India - english
Mon Oct 23 02:52:41 2017
Mon Oct 23 02:52:41 2017
LINETRAXX® RCMA420

LINETRAXX® RCMA420

The AC/DC sensitive residual current monitor RCMA420 is designed for monitoring earthed power supply systems (TN and TT systems) where smooth DC fault currents or residual currents continuously greater than zero may occur. These are in particular loads containing six-pulse rectifiers or one way rectifiers with smoothing, such as converters, battery chargers, construction site equipment with frequency-controlled drives. Currents in single conductors can be monitored too.

The prewarning stage (50…100 % of the set response value IΔn2) allow to distinguish between prewarning and alarm. Since the values are measured with measuring current transformers, the device is nearly independent of the load current and the nominal voltage of the system.

  • Features
  • Applications
  • Accessories
  • Ordering information
  • Downloads
  • AC/DC sensitive residual current monitor Type B acc. to IEC 62020 and IEC/TR 60755
  • r.m.s. value measurement (AC+DC)
  • Two separately adjustable response values 10…500 mA
  • Frequency range 0…2000 Hz
  • Start-up delay, response delay and delay on release
  • Digital measured value display via LC display
  • Measured value memory for operating value
  • CT connection monitoring
  • LEDs: Power On, Alarm 1, Alarm 2
  • Internal/external test/reset button
  • Two separate alarm relays (one changeover contact each)
  • N/O or N/C operation and fault memory behaviour selectable
  • Continuous self monitoring
  • Multi-functional LC display
  • Password protection for device settings
  • Sealable transparent cover
  • Two-module enclosure (36 mm)
  • RoHS compliant
  • Push-wire terminal (two terminals per connection)
  • AC/DC sensitive residual current monitoring in earthed two, three or four conductor systems (TN and TT systems)
  • Monitoring of variable-speed drives, UPS systems, construction site equipment, printing machines, battery systems, laboratory equipment, wood working machines, MF welding systems, furniture industry, medical electrical equipment, etc.
  • AC/DC sensitive current monitoring of single conductors de-energised under normal conditions (e.g. N and PE conductors)

 

Optional accessories for LINETRAXX® RCMA420

Measuring current transformers
TypeInternal diameter (mm)Art. No.
W20ABø 20B98080008
W35ABø 35B98080016
W60ABø 60B98080026

Connection cable measuring current transformer – RCMA420-D
TypeLength/mArt. No.
WX-1001B98080503
WX-2502,5B98080504
WX-5005B98080505
WX-100010B98080511

Accessories
TypeArt. No.
Mounting clip for XM420 enclosureB98060008
Snap-on mounting W20…, W35…B98080501
Snap-on mounting W60…B98080502

Variants of LINETRAXX® RCMA420


TypeResponse range IΔnFrequency rangeSupply voltage US*Art. No.**
RCMA420-D-110…500 mA0…2000 HzDC 9,6…94 V /
AC 16…72 V, 42…460 Hz
B74043001
B94043001
RCMA420-D-210…500 mA0…2000 HzDC 70…300 V /
AC 70…300 V, 42…460 Hz
B74043002
B94043002
* Absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)